An Improved AC System Strength Measure for Evaluation of Power Stability and Temporary Overvoltage in Hybrid Multi-Infeed HVDC Systems
2021 · IEEE Transactions on Power Delivery
저자
Yong-Kyu Kim, 이규섭 (Gyu‐Sub Lee), Chan‐Ki Kim, Seung‐Il Moon
연구주제
HVDC Systems and Fault Protection · Power System Optimization and Stability
NTIS 과학기술표준분류
에너지/자원만에너지·환경·원자력 확장
지원 과제·AI 키워드로 잡을 근거가 없어 분류하지 않았다.
AI 연구 키워드·방법
multi infeed high voltage direct current system 단락비(SCR) 계통 강도 temporary overvoltage
quasi steady state analysis time domain simulation
키워드 (OpenAlex)
power system stability temporary overvoltage reactive power support quasi-steady-state analysis dynamic simulation
초록
We developed a new strength measure, the hybrid multi-infeed effective short-circuit ratio (HMESCR), for evaluating hybrid multi-infeed high-voltage direct current (MIDC) systems. The HMESCR defines the strength of hybrid MIDC systems with line-commutated converter (LCC) high-voltage direct current (HVDC) and voltage-source converter (VSC) HVDC systems. Unlike previous measures, the HMESCR considers the capacity of VSC HVDC systems to provide reactive power and thus, enhance the strength of AC systems connected at different buses with LCC HVDC systems. To demonstrate how the HMESCR reflects power stability (PS) and temporary overvoltage (TOV), we used MATLAB/Simulink software to perform quasi-steady-state analyses and dynamic simulations. The HMESCR can be used to determine the strength of hybrid MIDC systems.
이 논문을 지원한 국가R&D 과제 (NTIS 성과)
NTIS 성과DB(2020–24)에서 DOI 매칭 없음
인접 그래프
노드 hover = 이웃 강조 · 1회 클릭 = 고정 · 고정된 노드 다시 클릭 = 페이지 이동
이 문서와 연결된 페이지
교수 1
연구주제 1
HVDC Systems and Fault Protection